Electric heat pump, reversible, Air/Air, in the heating mode it takes heat from the Outdoor Air and transfers it to the Indoor Air, in cooling mode it takes heat from the Indoor Air and transfers it to the Outdoor Air, consists of outdoor and indoor unit, OUTDOOR UNIT DATA: nominal heat output 39 kW (A7/A20), COP 4.45 (A7/A20), nominal cooling output 35 kW (A35/A27), EER 4.02 (A35/A27), max. electrical power consumption 12 kW, max. sound power 60.2 dB(A), operating temperature of outside air in heating mode -25/+35°C, operating temperature of outside air in cooling mode +18/+46°C, refrigerant type R32, max. distance to indoor unit 30 m, dimensions 1791x641xH1257 mm, weight 270 kg, INDOOR UNIT DATA: maks. air flow 6000 m³/h, max. sound power 59.6 dB(A), dimensions 1253x825xH1139 mm, weight 110 kg
Vai jūs interesē šis produkts? Sazinieties ar mums:

Roberts Priekulis

LV, RU, EN
+371 286 22395

Tirdzniecības pārstāvis Latvijā Saņemt piedāvājumu
Noklikšķiniet uz modeļa: parādīsies tehniskā informācija, izmēri, piederumi
e-NextPro - reversible, Air/Air, in the heating mode it takes heat from the Outdoor Air and transfers it to the Indoor Air, in cooling mode it takes heat from the Indoor Air and transfers it to the Outdoor Air, consists of outdoor and indoor unit
e-NextPro 40 OUTDOOR UNIT DATA: nominal heat output 39 kW (A7/A20), COP 4.45 (A7/A20), nominal cooling output 35 kW (A35/A27), EER 4.02 (A35/A27), max. electrical power consumption 12 kW, max. sound power 60.2 dB(A), operating temperature of outside air in heating mode -25/+35°C, operating temperature of outside air in cooling mode +18/+46°C, refrigerant type R32, max. distance to indoor unit 30 m, dimensions 1791x641xH1257 mm, weight 270 kg, INDOOR UNIT DATA: maks. air flow 6000 m³/h, max. sound power 59.6 dB(A), dimensions 1253x825xH1139 mm, weight 110 kg
e-NextPro 40
OUTDOOR UNIT DATA: nominal heat output 39 kW (A7/A20), COP 4.45 (A7/A20), nominal cooling output 35 kW (A35/A27), EER 4.02 (A35/A27), max. electrical power consumption 12 kW, max. sound power 60.2 dB(A), operating temperature of outside air in heating mode -25/+35°C, operating temperature of outside air in cooling mode +18/+46°C, refrigerant type R32, max. distance to indoor unit 30 m, dimensions 1791x641xH1257 mm, weight 270 kg, INDOOR UNIT DATA: maks. air flow 6000 m³/h, max. sound power 59.6 dB(A), dimensions 1253x825xH1139 mm, weight 110 kg
Modelis: e-NextPro 40
Vispārējie dati
Nominal heating output at 7°C outdoor and 20°C indoor air temperature
kW
39
Nominal heating output at -7°C outdoor and 20°C indoor air temperature
kW
32
COP - heating coefficient of performance at 7°C outdoor and 20°C indoor air temperature
4,45
COP - heating coefficient of performance at -7°C outdoor and 20°C indoor air temperature
3,20
Nominal cooling output at 35°C outdoor and 27°C indoor air temperature
kW
35
EER - cooling energy efficiency ratio at 35°C outdoor and 27°C indoor air temperature
4,02
Max. electrical power consumption
kW
12
Compressor system
Type
Scroll inverter vapor injection
Refrigerant type
R32
Refrigerant GWP
675
Refrigerant quantity if distance between outdoor and indoor unit does not exceed 10 m
kg
7,4
Outdoor unit fan data
Maks. gaisa plūsma
m³/st.
15000
Max. sound power level
dB(A)
60,2
Ventilatora tips
Axial inverter
Nominal diameter
mm Ø
910
Indoor unit fan data
Maks. gaisa plūsma
m³/st.
6000
Max. sound power level
dB(A)
59,6
Ventilatora tips
Axial inverter BLDC
Nominal diameter
mm Ø
800
Instalācijas dati
Power supply
V / Hz / Ph
400 / 50 / 3
Max. electrical power consumption
kW
12
Gas coolant connection diameter
Ø mm (")
22 (7/8)
Liquid coolant connection diameter
Ø mm (")
16 (5/8)
Max. coolant connection length between outdoor and indoor unit
m
30
Operating temperature range in heating mode
°C
-25 / +35
Operating temperature range in cooling mode
°C
+18 / +46
Outdoor unit dimensions
Platums
mm
1791
Dziļums
mm
641
Augstums
mm
1257
Svars
kg
270
Indoor unit dimensions
Platums
mm
1253
Dziļums
mm
825
Augstums
mm
1139
Svars
kg
110
e-NextPro electric heat pump Air/Air
Katalogi 410 KB
Modelis: e-NextPro 40
Montāžas kronšteini
SBR Floor stand for e-NextPro 40 heat pump outdoor unit, dimensions 250x130x95 mm
SBR
Floor stand for e-NextPro 40 heat pump outdoor unit, dimensions 250x130x95 mm
KRON WALL e-NextPro Outdoor Wall brackets for e-NextPro 40 heat pump outdoor unit, dimensions 1200x700 mm
KRON WALL e-NextPro Outdoor
Wall brackets for e-NextPro 40 heat pump outdoor unit, dimensions 1200x700 mm
KRON WALL e-NextPro Indoor Wall brackets for e-NextPro 40 heat pump indoor unit, dimensions 1000x450 mm
KRON WALL e-NextPro Indoor
Wall brackets for e-NextPro 40 heat pump indoor unit, dimensions 1000x450 mm
Additional accessories for e-NextPro heat pumps
PGD Digital control panel for e-NextPro heat pumps
PGD
Digital control panel for e-NextPro heat pumps
EL.CV_PT20 20 m length cable for PGD control panel connection
EL.CV_PT20
20 m length cable for PGD control panel connection
RCC Digital control panel for e-NextPro heat pumps, 7" touch display
RCC
Digital control panel for e-NextPro heat pumps, 7" touch display
HCC-F02 Metal wall frame for RCC control panel
HCC-F02
Metal wall frame for RCC control panel
Multi RCC Digital control panel for centralized control of e-NextPro heat pumps, can control up to 15 units, 15.6" touch display
Multi RCC
Digital control panel for centralized control of e-NextPro heat pumps, can control up to 15 units, 15.6" touch display
O-SLT002 Electronic communication board for e-NextPro heat pumps connection to Multi RCC control panel
O-SLT002
Electronic communication board for e-NextPro heat pumps connection to Multi RCC control panel